Chemistry · Thermal Engineering · HVAC

Heat Load Diversity Factor Calculator

Compare equipment peaks, identify coincident demand, and estimate plant capacity.

Calculation Results

Schedule-based analysis

Hourly thermal demand

Peak and plant sizing

Hourly load profile

HourTotal heat demandShare of peak

Calculation Settings

All load inputs use your selected unit. COP may exceed 1 for heat pumps or chillers. Seasonal multipliers affect demand and displayed costs.

Equipment and zone loads

Operating hours use a 24-hour local daily clock. End times before start cross midnight. Operating fractions represent typical demand while scheduled.

NameGroupPeak loadConnected loadStart (h)End (h)Duty %Enabled

Optional measured hourly data

Upload a CSV with an hour column (0–23) and one or more numeric equipment-load columns. All samples must share synchronized timestamps. Imported loads use the selected unit and take precedence in schedule mode.

No imported profile.

Scenario and sensitivity comparison

ScenarioDiversity factorCoincident demandPlant capacityAnnual energy cost
Alternative scenarios vary the coincidence assumption by ±10% for screening. These are not measured schedules.

Formula Used

Diversity factor = sum of individual maximum loads ÷ coincident maximum demand.

Coincidence factor = coincident maximum demand ÷ sum of individual maxima.

Demand factor = coincident maximum demand ÷ connected load.

Required plant output = coincident load × (1 + margin) × (1 + expansion).

Estimated purchased energy = delivered thermal energy ÷ efficiency (or COP).

The sizing margin is deliberately multiplicative. Plant capacity is useful thermal output, not electricity input. Heating and cooling demands must be evaluated independently unless verified heat recovery exists.

How to Use This Calculator

  1. Select the correct heating, cooling, or process system.
  2. Enter individual equipment peaks and connected capacities.
  3. Set schedules, duty factors, and seasonal conditions.
  4. Choose schedule, measured, inverse, or target-capacity analysis.
  5. Review demand, factors, plant sizing, and hourly charts.
  6. Compare assumptions and export results as CSV or PDF.

Example Table

Example EquipmentIndividual maximum
Reactor heating120 kW
Process hot water80 kW
Industrial dryer150 kW
Space heating100 kW
Cleaning system50 kW
Summed individual peaks500 kW
Illustrative coincident peak350 kW
Diversity factor1.429
Plant at 10% margin385 kW

Illustrative 350 kW coincident demand is an independent assumption, not derivable from maxima alone.

Understanding Heat Load Diversity

Why Diversity Matters

Heat load diversity describes how thermal peaks occur across connected equipment. Individual maximum loads rarely occur during the same hour. This difference can significantly affect heating and cooling plant sizing. Engineers use synchronized profiles to identify actual simultaneous demand.

Understanding the Key Factors

The diversity factor equals summed individual maxima divided by the coincident maximum. The coincidence factor is its reciprocal. Both describe timing relationships, not equipment efficiency. Demand factor instead compares maximum system demand against total connected capacity. Consistent definitions prevent misleading comparisons between industrial and building applications.

Building a Useful Profile

Enter each equipment name and its rated maximum thermal load. Choose a daily schedule, operating fraction, and equipment group. The calculator builds representative hourly demand profiles for each device. It then adds equipment demand at matching hours. The largest hourly total becomes the coincident peak. Alternatively, enter a measured coincident peak for direct calculation.

Engineering Applications

Chemical reactors, dryers, cleaning systems, boilers, and HVAC zones often have different schedules. Scheduling can reduce simultaneous demand without reducing process energy. Actual operating controls, production changes, and startup surges may alter peaks. Imported measured load profiles provide stronger evidence than typical schedules.

Selecting Equipment Capacity

Plant sizing should consider the coincident thermal peak plus appropriate allowances. A safety margin provides limited extra capacity for uncertainty. Future expansion can be evaluated separately. System efficiency converts delivered thermal energy into purchased energy. Do not multiply thermal demand by efficiency when selecting useful output capacity.

Visualizing System Demand

The hourly chart reveals why total installed peak exceeds simultaneous demand. Scenario comparisons show how operating schedules affect capacity needs. Seasonal multipliers provide preliminary screening rather than detailed weather simulation. Review heat recovery, standby use, and simultaneous heating and cooling separately. This tool supports early engineering decisions, not detailed equipment certification.

Reporting and Verification

Export calculations for review, including assumptions, equipment details, and time series. Verify important sizing choices against measured records and applicable standards. Document operating constraints before final plant selection.

Frequently Asked Questions

1. What is a heat load diversity factor?

It is the sum of individual peak loads divided by the maximum simultaneous combined load.

2. Can diversity factor be below one?

Not for consistent nonnegative load profiles under the stated sum-of-peaks convention.

3. How does coincidence factor differ?

It is the reciprocal of the diversity factor, usually between zero and one.

4. What is demand factor?

Maximum simultaneous demand divided by summed connected equipment capacity.

5. Does diversity reduce annual thermal energy?

No. Rescheduling may reduce peak demand without changing total delivered energy.

6. Can heating and cooling be combined?

Analyze them separately for independent plants. Do not cancel opposite thermal demands without a validated heat-recovery model.

7. How accurate are daily schedules?

They are screening approximations. Hourly measured profiles provide stronger evidence.

8. How should I size a boiler or chiller?

Use the relevant coincident thermal peak plus justified margins, then check redundancy and design conditions.

9. Is diversity factor the same as usage diversity?

No. Some sources call coincidence percentage usage diversity; this calculator labels each explicitly.

10. What does the reserve percentage mean?

It describes additional specified capacity above estimated coincident peak demand.